Onboard inputs and outputs
UIO Universal inputs and outputs support the following signal types:
● Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (375, 385), NTC 10k (Type II / Beta (0-50 °C) =
3892 K), NTC 100k
● Resistance sensors 1000 Ohm, 2500 Ohm, 1000...1175 Ohm (for setpoint shift)
● Voltage input analog DC 0…10 V
● Current measurement analog DC 0...20 mA or 4...20 mA, (inputs U1, U2, U7, U8)
● Binary potential-free contacts for signaling functions
● Counter to 25 Hz (electronic switch to 100 Hz)
● Analog outputs DC 0…10 V
DO Relay outputs for binary controls, changeover contact
(NO, NC, pulse)
Equipment combinations
TXM I/O modules
Description Type
1)
Data sheet
Digital input module 8 or 16 I/O points TXM1.8D, TXM1.16D CM2N8172
Universal module without / with local operation and LCD TXM1.8U, TXM1.8U-ML CM2N8173
Super universal module without / with local operation and LCD TXM1.8X, TXM1.8X-ML CM2N8174
Relay module without / with local operation TXM1.6R, TXM1.6R-M CM2N8175
Resistance measuring module (for Pt100 4-wire) TXM1.8P CM2N8176
Triac module TXM1.8T CM2N8179
Digital input and relay module TXM1.4D3R CM2N8188
Power module TXS1.12F10 CM2N8183
Bus connection module TXS1.EF10 CM2N8183
Island bus extension module TXA1.IBE CM2N8184
1)
Module series B and higher. In following use cases only series D can be used (available as of 2012):
● I/O bus communication mode "Event"
PXC4 can power TXM extensions modules. For further details see PXC4, PXC5 & PXC7 Planning overview
A6V13054435 and data sheets.