6
Siemens Schweiz AG A6V11937668_en--_l
Smart Infrastructure 2023-12-22
LED displays
Activity LED Color Activity Function
RUN Green Continuously ON
Continuously OFF
Flashing
Device operational
Device not operational
Start-up or program halted
Red Continuously OFF
Continuously ON
Rapid flashing
OK
HW or SW fault
Firmware or application missing/corrupted
MSTP Yellow Flashing
Continuously OFF
Communication BACnet MS/TP
No communication
COM TX
(PXC4.M16)
Yellow Flashing
Continuously OFF
Communication
No communication to subsystem
COM RX
(PXC4.M16)
Yellow
SVC Red Continuously OFF
Flashing
OK
Device is not configured
Flashing per wink
command
Identification of device after receipt of wink
command
WLAN Blue Steady OFF
Steady ON
Flashing
WLAN inactive
WLAN active and at least one WLAN client
connected
WLAN active and no WLAN client connected
Service button Press 0.2 ... 1 s
Press 1 ... 3 s
Identification in the network
Enable/ disable WLAN
WLAN is disabled automatically after 10min, if
no client is connected
As per description Do the following to reset the device to factory
state:
1. Power off the device.
2. Power on the device.
3. Wait until all LEDs light up and turn off
again, then press the Service button.
4. Keep the Service button pressed until all
LEDs light up, then release the button.
All LEDs go off, the device restarts.
5. Wait until the device has fully started –
unconfigured (green RUN LED and red
SVC LED are flashing)
Product documentation
Related documents such as the environmental declarations, declarations of conformity, etc.,
can be downloaded from the following Internet address:
www.siemens.com/bt/download