EasyManua.ls Logo

Siemens Desigo PXC4.M16 - Warranty; Function Data

Siemens Desigo PXC4.M16
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
Siemens Schweiz AG A6V11937668_en--_l
Smart Infrastructure 2023-12-22
Warranty
The application-specific technical data is guaranteed only in combination with the Siemens
products listed in the 'Device combinations' section. If third-party products are used, any
guarantee provided by Siemens will be invalidated.
Technical data
Power supply
Operating voltage (24 V~, , ) AC 24V -15 / +20% (PELV)
AC 24V Class 2 (US)
48…63 Hz
Operating voltage DC 24 V (24 V, , ) DC 24V -15 / +20% (PELV)
DC 24V Class 2 (US)
Functional ground(US)
Functional earth
The terminal for the functional ground must be
connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to Max. 2.5 mm
2
(14 AWG)
Internal fusing 4 A irreversible / non-replaceable
External supply line fusing (EU) Non-renewable fuse max. 10A slow-blow
or
circuit breaker max. 13A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10A
Protection Reverse connection protection for DC 24V
Power consumption (for transformer planning)
Operating voltage PXC4.M16S PXC4.M16
AC 24 V DC 24 V AC 24 V DC 24 V
Full load 76 VA / 3.2 A 65 W / 2.7 A 80 VA / 3.3 A 67 W / 2.8 A
Base load
PXC4.M16S: without loading by I/O modules
TXM and field devices
PXC4.M16: without loading by I/O modules
TXM, KNX PL-Link, and field devices
8 VA / 0.33 A 5 W / 0.2 A 8 VA / 0.33 A 5 W / 0.2 A
Field device supply V+ (DC 24 V, 100 mA)
(terminals 8 and 19)
5VA / 0.2A 3 W / 0.13 A 5 VA / 0.2 A 3 W / 0.13 A
Field device supply V
(terminals 18 and 29)
48 VA / 2 A 48 W / 2 A 48 VA / 2 A 48 W / 2 A
I/O modules TXM supply 15 VA / 0.6 A 8.5 W / 0.35 A 15 VA / 0.6 A 8.5 W / 0.35 A
KNX PL-Link supply 4 VA / 0.17 A 2.2 W / 0.09 A
Function data
Hardware information PXC4.M16, PXC4.M16S
Processor Texas Instruments AM335x, 300 MHz
Storage 128 MByte RAM
512 MByte Flash
Data backup in the event of power failure
Energy reserve (supercap) to support real-time clock (7 days).
Data available if stored to flash memory. Occurs every 5 minutes.
The interval of 5 minutes is only valid for change log but not for trending.
In case of a power failure, trend log data can be lost up to 30 minutes.

Other manuals for Siemens Desigo PXC4.M16