Examples of connection diagrams for universal inputs/outputs
Feedback contact (NO)
Feedback contact (NC)
Counter inputs, that count faster than 1 Hz and are laid with more than 10 meters using analog inputs in
the same cable duct, must be shielded.
Temperature sensor LG-Ni 1000
Temperature sensor, general
Resistance transmitter
Active sensor powered by the automation station
Active sensor with external power
Do NOT ground external power (ground loops)
Active sensors 0 ... 20 mA or 4 ... 20 mA (2-wire)
On U1, U2, U7, U8 only
Device with input DC 0...10 V
General device with control input DC 0...10 V,
Powered by the automation station
General device with control input DC 0...10 V,
Do NOT ground external power (ground loops)
Technical data on specific applications are valid only together with Siemens products listed
under "Equipment combinations". Siemens rejects any and all warranties in the event that
third-party products are used.