System controller to integrate Modbus and MS/TP devices
Technical and mechanical design
The compact build allows for mounting the devices on a standard rail or a wall.
4
5 6
15 1413
10
12
1
3
2
7
9
8
11
16
Date/Series
S/N
WLAN
Default
Plug-in terminal block with screw terminals
KNX, PL-link, for future use
Plug-in terminal block with screw terminals
Power supply
Plug-in terminal blocks with screw terminals
Universal inputs/outputs, field device supply
Connector for I/O modules TXM
Plug-in terminal block with screw terminals
Relay outputs
Plug-in terminal block with screw terminals
COM, Modbus RTU
Plug-in terminal block with screw terminals
MS/TP
DIP switch for bus termination and polarization
COM, MS/TP
Slider for mounting on DIN rails
Service button (identification in network and
WLAN on/off)
Date / Series and Serial number
LEDs for communication and state
QR code for default WLAN access (description
see Technical data)
Continuously ON
Continuously OFF
Flashing
Device operational
Device not operational
Start-up or program halted
Continuously OFF
Continuously ON
Rapid flashing
OK
HW or SW fault
Firmware or application missing/corrupted
Flashing
Continuously OFF
Communication BACnet MS/TP
No communication
Flashing
Continuously OFF
Communication
No communication to subsystem
Continuously OFF
Flashing
OK
Device is not configured
Flashing per wink
command
Identification of device after receipt of wink
command