Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
● Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be at least 10 K (18° F) lower
outside the installation box.
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits!
● Adapt the wire cross sections as per local regulations to the rated value of the installed
fuse.
The relay outputs may be connected to mains voltage
Risk of electrical shock!
● Use terminal covers or install the device in a lockable cabinet.
The device is considered an electronic device for disposal in accordance
with the European Guidelines and may not be disposed of as domestic
garbage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations.
Operating voltage (24 V~, ⏊, )
AC 24 V -15 / +20 % (SELV / PELV) or
AC 24 V Class 2 (US)
48…63 Hz
Functional ground (US)
Functional earth
The terminal for the functional ground must be
connected on the installation side with the building
grounding system (PE).
Screw terminals for wire cross sections up to
4 A irreversible / non-replaceable
External supply line fusing (EU)
Non-renewable fuse max. 10 A slow-blow
or
circuit breaker max. 13 A
Tripping characteristic B, C, D per EN 60898
or
Power supply with current limitation of max. 10 A