Power consumption (for transformer planning)
Base load (without loading by I/O modules TXM and
field devices)
Field device supply V+ (DC 24 V, 100 mA)
(terminals 8 and 19)
Field device supply V~ (AC 24 V, 2 A)
(terminals 18 and 29)
Texas Instruments AM335x, 300 MHz
128 MByte SDRAM (DDR3)
512 MByte NAND Flash
Data backup in the event of power failure
Energy reserve (supercap) to support real-time clock (7 days).
Data available if stored to flash memory. Occurs every 5 minutes.
Cu-wire or Cu-strand with wire end sleeve
1 x 0.6 mm ∅ to 2.5 mm
2
(22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.0 mm
2
(22 to 18 AWG)
Cu-strand without wire end sleeve
1 x 0.6 mm ∅ to 2.5 mm
2
(22 to 14 AWG)
or 2 x 0.6 mm ∅ to 1.5 mm
2
(22 to 16 AWG)
6...7.5 mm (0.24...0.29 in)
Slot screws, screwdriver size 1
EIA-485, electrically isolated
9600, 19200, 38400, 57600, 76800, 115200 (depending
on the configuration)
120 Ohm, switchable with DIP switch
Internal bus polarization
270 Ohm pull-up/pull-down resistances, switchable with
DIP switch
Cabling (in-house cabling only)
Distance between 2 devices
Length of the MS/TP line
3-wire cable, shielded
Max. 500 m (1650 ft)
Max. 1000 m (3300 ft)
Short-circuit proof
Protection against faulty wiring with AC 24 V
EIA-485, electrically isolated
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
(depending on the configuration)
120 Ohm, switchable with DIP switch