Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02
Building Technologies Sources of errors 23 Sep 2011
Sources of errors
Possible causes:
Room unit exhausted poor light conditions
Check documentation on room unit
RF link faulty distance, interference emitters
Check documentation on room unit
Room unit not / incorrectly learned-in in the gateway (SensorID)
Room unit faulty
Impact on the system:
When UCPTenoceanRcvTm has elapsed, nvoAlarmSensor is set (evaluation
optional).
T0 --
T1 Last valid value from T0; otherwise 0.0 C
T2 With SCPTmaxSendTime T1
Without SCPTmaxSendTime invalid (327.7 C) after RXC heartbeat
has elapsed (60 min)
T3 Ditto; if 0.0 C frost alarm
Possible causes:
Gateway has no power (power_fail)
Bus interruption
Error in configuration of gateway
Gateway faulty
Impact on the system:
T0 --
T1 --
T2 Invalid (327.7 C) after RXC heartbeat has elapsed (60 min)
power_fail gateway:
nvo_temp_p = 0.0 C until room unit sends again (up to approx. 20 min.)
Ohne SCPTmaxSendTime T2 = last valid T2
SCPTmaxSendTime < approx. 20 min T2 = 0.0 C (frost alarm)
SCPTmaxSendTime > approx. 30 min T2 = last valid T2
T3 Ditto; at 0.0 C frost alarm
F1:
Gateway receives no
telegrams from the
room unit
F2:
RXC receives no
L
ONWORKS telegrams
from the gateway