Siemens RXZ95.1/LON – Gateway EnOcean/LonWorks CM2N1661en_02
Building Technologies System requirements 23 Sep 2011
System requirements
SRC04-FTT plug-in (template: Thermokon srcn_9_1_02)
Functions:
Monitoring and configuration gateway / room units
For use with RXT10 tool or standard LNS tool
The device resource files contain information about supplier-specific configuration
parameters and network variables (UNVTs and UCTPs).
Prerequisite for installation is L
ONMARK® resource files version 13.00 or,
alternatively, LonM
ARK resource file API version 2.3 (bothersome installation).
srcn_9_1_02.APB; .NXE; .XFB; .XIF; .PDF (if SRC-FTT plug-in is not used)
LNS plug-in, device resource files, L
ONWORKS application:
Download from the DESIGO RX intranet:https://intranet10.sbt.siemens.com/
https://intra.industry.siemens.com/bt/global/en/bus
iness/building_comfort/systems/
desigo/ra/Pages/des-ra-units.aspx?TabcardNo=6
L
ONMARK resource files version 13.00:
Download from http://www.lonmark.org/technical_resources/resource_files/
Environment for engineering tool
Integration of QAX95.x/QAX96.x: The RXT10 tool or a standard LNS tool can be
used.
Integration of QAX97.x/QAX98.x: A standard LNS tool must be used.
Limitations
With a DESIGO system, it is not possible to integrate additional EnOcean
products, such as buttons, presence detectors, etc., via the RXZ95.1/LON
gateway with the RXT10 tool.
Reason: In the gateway, temperature and setpoint adjustment are
available as static network variables. However, additional
functions are configured dynamically, and the RXT10 does not
support dynamic network interfaces.
RXT10 does not support the multifunctional button of the QAX97.4 und QAX98.4
room units.
For technological reasons, the control performance of an RXC… room controller
in connection with an EnOcean room unit is inferior to that with a standard
QAX3x room unit
Software LNS PlugIn
Device resource files:
Thermokon_DRF22.exe
L
ONWORKS application
Software source /
documentation