Connection
4.10 Connecting the IM 154-4 PN High Feature Interface Module with CM IM PN PP FO
ET 200pro distributed I/O system
Operating Instructions, 03/2013, A5E00335544-08
103
4.10
Connecting the IM 154-4 PN High Feature Interface Module with
CM IM PN PP FO
Introduction
You connect the power supplies and PROFINET IO (optically via fiber-optic cables) to the
CM IM PN PP FO connection module. The IM 154-4 High Feature interface module is
equipped with an internal PROFINET switch. This allows direct looping through of
PROFINET IO, or the direct connection of a further IO device.
X03 DC 24V Push-
pull socket (with male connector) for feeding the 1L+ electronics/encoder supply
and the 2L+ load voltage supply
X04 DC 24V Push-pull socket (with male connector) for looping the 1L+ electronics/encoder supply
and the 2L+ load voltage supply
X02 P1 R
Push-pull socket for SC RJ for feeding of PROFINET IO (fiber-optic cable)
X02 P2 R
Push-pull socket for SC RJ for looping through of PROFINET IO (fiber-optic cable)
Requirements
The IM 154-4 High Feature interface module (including the bus module) and the
CM IM PN PP FO connection module have been installed on the rack.
Required tools
Screwdriver
Stripping tool for wiring the push-pull cable connector, if you are fabricating your own
cables.