Commissioning and Diagnostics
6-44
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 6-16 1SSI
Error Type What to DoMeaning
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.
26
D
11010: External fault Start/stop bit error (absolute
position encoder error): Wire
break in the sensor cable or
sensor cable is not connected.
Sensor type, transmission rate,
and monoflop time do not
correspond to the sensor
connected; programmable
sensors do not correspond to the
settings on the 1SSI EM. Sensor
is defective or there are faults.
Replace the sensor; correct the
process wiring.
Correct the parameter
assignment.
1Count 24V/100kHz
Table 6-17 1Count 24V/100kHz
Error Type
Meaning What to Do
1
D
00001: Short circuit Short circuit of the sensor
supply or the actuator.
Check the wiring to the sensor.
Correct the process wiring.
5
D
00101: Temperature rise Digital output is overloaded. Correct the process wiring.
6
D
00110: Open circuit Line to the actuator interrupted. Correct the process wiring.
9
D
01001: Error Internal module error occurred.
Load voltage from the power
module is too low.
Replace the module.
Correct the process wiring.
Check the load voltage.
16
D
10000: Parameter
assignment error
Parameters have not been
assigned to the module.
Adjust the parameter
assignment.
1Count 5V/500kHz
Table 6-18 1Count 5V/500kHz
Error Type
Meaning What to Do
1
D
00001: Short circuit Short circuit of the sensor
supply or the actuator.
Check the wiring to the sensor.
Correct the process wiring.
5
D
00101: Temperature rise Digital output is overloaded. Correct the process wiring.
6
D
00110: Open circuit Line to the actuator interrupted. Correct the process wiring.
9
D
01001: Error Internal module error occurred. Replace the module.