EasyManua.ls Logo

Siemens ET 200SP HA - Displays and interrupts; 6.1 Status and error displays

Siemens ET 200SP HA
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.5 Con󹪝guration limit for IO devices
3.5.1 Maximum number of connections to IO controllers
De󹪝nition
A maximum of 4 IO controllers are allowed to be connected to the IO device.
3.5.2 Maximum permissible bytes
De󹪝nition
The maximum bytes in the input data area or for bytes in the output data area depend on the
following:
Connection type
Number of IO controllers with connection to the shared device
Con󹪝guration in Run
Description
The following maximum permissible number of bytes are available in the input data area or for
bytes in the output data area:
Connection type Number of IO controllers with
connection to the shared de‐
vice
Requirement for the input data or out‐
put data
Without system redun‐
dancy
1 IO controller Maximum of 1440 bytes each
2 IO controllers Maximum of 1440 bytes for each control‐
ler
3 or 4 IO controllers Maximum of 360 bytes each
System redundancy S2 1 redundant IO controller Maximum of 1000 bytes each
1 redundant IO controller and
1 additional IO controller
Maximum of 360 bytes each
System redundancy R1 Maximum of 1440 bytes each
See also
Online Support (
https://support.industry.siemens.com/cs/ww/en/view/109760425)
Product overview
3.5 Con󹪝guration limit for IO devices
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE 19

Other manuals for Siemens ET 200SP HA

Related product manuals