Product overview
3
3.1 Interface module
De󹪝nition
The IM 155‑6 PN HA, together with the carrier and BusAdapter, forms the interface of the
ET 200SP HA.
The interface is used for communication between the CPU and the connected ET 200SP HA I/O
modules via PROFINET IO.
In addition to the technical speci󹪝cations, this module has the following properties:
Supply voltage 1L+ 24 V DC (SELV/PELV).
The supply voltage is fed via the carrier module.
The connection plug is included in the scope of delivery of the interface module.
Firmware update
Pulling and plugging modules in RUN
Value status QI
Multi Hot Swap (pulling/plugging of multiple I/O modules during operation)
Saving service data
Recording the value status of I/O modules
Reference temperature distribution
Note
The IM 155‑6 PN HA cannot be pulled/plugged when the associated connector for the supply
voltage is plugged in.
In addition to the technical speci󹪝cations, this module supports the following PROFINET IO
functions:
Supported Ethernet services: ping, arp, network diagnostics (SNMP)/MIB-2, LLDP-MIB and
MRP-MIB
Port diagnostics
Disabling of ports
Minimum update time of 250 µs
Device replacement without programming device (PG)
Reset to factory settings via PROFINET IO
Support of submodules on suitable I/O modules
Shared Device (as of FW V1.1)
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE 9