Configuring/address space
4.9 Explanation of parameters
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
128 Manual, 05/2019, A5E35061186-AB
4.9 Explanation of parameters
4.9.1 Channel configuration
Channel configuration
This parameter is used to specify whether both channels are to be connected in parallel.
Channel configuration
Meaning
2 channels (2 A)
(default)
The two channels operate separately and each has a maximum output
current of 2 A.
1 channel (4 A) The two channels are connected in parallel and operate as a logical
channel with a maximum output current of 4 A.
All parameter settings and operations that use the control interface
must use addresses with Channel 0. Feedback signals are only pro-
vided for Channel 0.
The control and feedback interface is limited to one channel only.
Channel 1 cannot be configured or operated.
Current measurement adds the measured values of both channels.
Note
High-speed output
The "High
-Speed Output (0.1 A)" can only be selected for the channel configuration "2
Channels (2 A)".