Interrupts/diagnostic messages
5.2 Diagnostic messages
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
147
Diagnostics alarm
Error
code
Meaning
Solution
Supply voltage
fault
110
H
Error at supply voltage L+
Possible causes:
Low voltage
Wiring of supply voltage L+ faulty
Check supply voltage L+ at the Ba-
seUnit
Check wiring of supply voltage L+
Overtemperature 506
H
Possible causes:
Short-circuit or overload at the digital out-
puts or output of the sensor supply
Ambient temperature outside specifications
Contamination in the module prevents
cooling
Check process wiring
Improve cooling
Check connected loads