Technical data FC700A
12
Siemens Building Technologies 007836_a_en_--.doc
Fire & Security Products 03.2004
4 Technical data FC700A
Operating voltage 115 / 230VAC ±15% 50... 60Hz
Power consumption 40... 220VA (per converter B2F020)
Battery operation in the event of mains failure
- Standard operating period
- Optional
12...24h
Up to 72h (see chapter 23)
Environmental conditions
Temperature during operation
Storage
Humidity
0°C... +40°C
-20°C... +60°C
Max. 95%, no condensation
Complies with class 3K5 according to IEC 721–3–3
IP protection category (EN 60529 / IEC 529)
- Control unit
- Remote control terminal
IP50
IP52 H26G220 cabinet
IP40 H28G200 cabinet
Dimensions
- Control unit cabinet
- Separate control terminal in cabinet H26G220
H28G200
W = 520mm, H = 602mm, D = 100mm / 155mm
W = 366mm, H = 219mm, D = 76mm
W = 520mm, H = 300mm, D = 70mm
Colors
- Control unit cabinet
- Operating unit front terminal B3Q700
- Control terminal cabinet H26G220
H28G200
H28T110/120
RAL 7035 light grey
Dark grey like Pantone 431C, Pantone 429C grey
Pantone 421 grey
RAL 7035 light grey
1E110 dark grey