2 Parameters
2.2 List of parameters
Description: Activates the readback input for the safety digital outputs (F-DO)
The test mode for the particular safety digital output is set in p10047.
Dependency: Refer to: p10047
Note: F-DO: Failsafe Digital Output
Description: Sets the test stop mode for the particular safety digital output (F-DO)
Index 0: F-DO 0
Index 1: F-DO 1
Index 2: F-DO 2
Index 3: F-DO 3
Value: 1: Test mode 1 evaluation of int. diagnostic signal (passive load)
2: Test mode 2 read back F-DO in DI (relay circuit)
3: Test mode 3 read back F-DO in DI (actuator with feedback signal)
Note: If value = 1:
When this test mode is being used, and excessive resistance of the load between DO+ and DO- can lead to
problems during the test stop. It is therefore important to make sure that the load resistance at an individual F-DO
does not exceed 10 kOhm.
Description: Configures the test stop for F-DI and F-DO of the TM54F.
If the automatic test stop is activated, then the test stop can still be started using binector input p10007.
Note:
The automatic test stop is started after power up, partial power up or a warm restart.
Value: 0: Manual test stop via BICO p10007
1: Automatic test stop
p10046 SI TM54F F-DO feedback signal input activation / SI F-DO FS act
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 2892
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Read back F-DO 0 Test active No test -
01 Read back F-DO 1 Test active No test -
02 Read back F-DO 2 Test active No test -
03 Read back F-DO 3 Test active No test -
p10047[0...3] SI TM54F F-DO test stop mode / SI F-DO test mode
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 3 2
p10048 SI TM54F F-DI F-DO test stop configuration / SI teststop config
TM54F_MA Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0