2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1058 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the communication status of the individual drives with the Terminal Module 54F (TM54F).
For r10055 = 0, the following applies:
All drives assigned in p10010 communicate with the TM54F.
Description: Display and BICO output for the status of the Terminal Module 54F (TM54F).
Description: Enters the Safety Integrated password for the Terminal Module 54F (TM54F).
This password is required to change the safety-relevant parameters.
r10055 SI TM54F communication status drive-specific / SI comm_stat drv
TM54F_MA,
TM54F_SL
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Communication between drive 1 and
TM54F
Not configured Configured -
01 Communication between drive 2 and
TM54F
Not configured Configured -
02 Communication between drive 3 and
TM54F
Not configured Configured -
03 Communication between drive 4 and
TM54F
Not configured Configured -
04 Communication between drive 5 and
TM54F
Not configured Configured -
05 Communication between drive 6 and
TM54F
Not configured Configured -
r10056.0 CO/BO: SI TM54F status / SI stat
TM54F_MA Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Test stop status Active Inactive -
p10061 SI TM54F password input / SI password inp
TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 2891
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex