Fig. 3-49 2483 – IF1 send telegram, free interconnection via BICO (p0922 = 999)
- 2483 -
Function diagram
87654321
fp_2483_54_eng.vsd
DO: A_INF, B_INF, CU_G, CU_S, R_INF, S_INF, TB30, TM15DI_DO, TM31, TM120, TM150
S120/S150/G130/G150
18.03.16 V04.08.00
PROFIdrive - IF1 send telegram, free interconnection via BICO (p0922 = 999)
PROFIdrive sampling time
PZD send word 7
PZD send word 24
PZD send word 25
PROFIBUS
PROFINET
Drive object n
Header
Drive object 1
Drive object 2
.
.
.
.
.
.
Drive object m
Trailer
PZD send word 1
PZD send word 2
PZD send word 3
PZD send word 4
PZD send word 5
PZD send word 6
PROFIdrive
send telegram
<4>
(0)
p2051[1]
(0)
p2051[2]
(0)
p2051[3]
(0)
p2051[4]
(0)
p2051[0]
Reference quantities for further interconnection
p200x
<3>
(0)
p2051[5]
(0)
p2051[6]
(0)
p2051[23]
(0)
p2051[24]
IF1 Diag send word
r2053[0...24]
...
<2>
<1>
<1> Not for G130/G150: TM15DI_DO, TM120.
Usable infeeds:
G130: none, G150: B_INF, S120: x_INF, S150: A_INF
<2> The number of PZD send words depends on the drive object type.
<3> The following representation applies for words: 4000 hex = 100 %.
The reference variables p200x apply for the ongoing interconnection (100 % -> p200x).
The following applies for temperature values: 100 °C -> 100 % = 4000 hex; 0 °C -> 0 %.
<4> Using the binector/connector converters at [2472], bits of 5 send words can be interconnected with any binectors.
<2>