SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
129
2 Parameters
2.2 List of parameters
Description: Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency: Refer to: F30002
Description: Selects the motor type or starts to read in the motor parameters for a motor with DRIVE-CLiQ (p0300 = 10000 or
10001, if there is a second data set).
For p0300 < 10000 the following applies:
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
5 = synchronous motor separately excited
7 = SIEMOSYN motor
8 = reluctance motor (for textile applications)
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/AOP).
The following applies for values < 100:
Motor data must be manually entered.
The following applies for values >= 100:
Motor data are automatically loaded from an internal list.
Value: 0: No motor
1: Induction motor
2: Synchronous motor
6: Synchronous reluctance motor
7: SIEMOSYN synchronous motor
8: Reluctance motor textile
10: 1LE1 induction motor (not a code number)
11: 1LA1 induction motor (not a code number)
12: 1LE2 induction motor (not a code number)
13: 1LG6 induction motor (not a code number)
14: 1xx1 SIMOTICS FD induction motor (not a code number)
15: 1LA5 induction motor (not a code number)
16: 1LA6 induction motor (not a code number)
17: 1LA7 induction motor (not a code number)
18: 1xx8 SIMOTICS TN induction motor (not a code number)
19: 1LA9 induction motor (not a code number)
100: 1LE1 induction motor
101: 1PC1 induction motor
102: 1PH2 induction motor
r0297 DC link voltage overvoltage threshold / Vdc U_upper_thresh
VECTOR_G, B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8750, 8760,
8850, 8864, 8950, 8964
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p0300[0...n] Motor type selection / Mot type sel
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 6310
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 10001 0