3 Function diagrams
3.28 Voltage Sensing Module (VSM)
SINAMICS G130/G150
1352 List Manual (LH2), 07/2016, A5E03263479A
Fig. 3-223 9886 – Temperature evaluation
- 9886 -
Function diagram
87654321
fp_9886_54_eng.vsd
S120/S150/G130/G150
11.02.16 V04.08.00
Voltage Sensing Module (VSM) - Temperature evaluation
DO: A_INF, S_INF, VECTOR
X520.5
X520.6
Hardware
smoothing 1 s
r3664.1
r3664.0
Software smoothing
0.5 s
2 mA
Sensor type
p3665 (0)
PTC resistor
threshold 1650 Ohm
Resistance
calculation
+
-
+ temp
-temp
<1>
r3666
VSM temp_act
0
1
0
1
<4>
<4>
<1> p3665
= 0: No sensor
= 1: PTC
= 2: KTY
= 6: PT1000
<2> A fault or alarm in the temperature evaluation of the VSM is communicated to the downstream evaluation using special temperature values.
<3> As a result of the wire breakage monitoring the maximum temperature that can be measured is limited to approximate 188.6 °C.
<4> PTC: A value > 250 °C de-activates the alarm or fault.
KTY/PT1000: A value > 188.6 °C de-activates the alarm or fault.
<5> Can only be used with chassis infeeds.
<6> The VECTOR drive object is assigned a dynamic index (p0150).
<5>
<6>
<6>
<6>
<6>
Temperature sensor
KTY/PT1000/PTC
Fault F34920
temperature sensor evaluation
<2>
Sensor type
p3665 (0)
Overtemperature alarm threshold
0...301 [°C]
p3667[0] (150)
A34211
"Temperature alarm
threshold exceeded"
F34207
"Temperature fault
threshold exceeded"
Overtemperature fault threshold
0...301 [°C]
p3668[1] (180)
Overtemperature hysteresis
p3669
-50 °C
1
0
250 °C
KTY
PTC
188.6 °C
-140 °C
<1>
<3>
<6>
No sensor
188.6 °C
-70 °C
R
T
<3>
PT1000
0
1
R
T
0
1
2
6
4000.00 μs
A
D
Alarm is not present
Alarm is present
-300 °C
1
0