EasyManua.ls Logo

Siemens G130 - F06909 Braking Module internal Vce fault; A06921 (N) Braking resistor phase unsymmetry; F06922 Braking resistor phase failure

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1533
4 Faults and alarms
4.2 List of faults and alarms
F06909 Braking Module internal Vce fault
Message value: %1
Message class: Braking Module faulted (14)
Drive object: B_INF
Component: None Propagation: GLOBAL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: In the power unit, the monitoring of the collector-emitter voltage (U_ce) of the power semiconductor to control the
braking resistor has responded.
Possible causes:
- short circuit at the braking resistor terminals.
- defective power semiconductor in the braking resistor control.
Note:
Under certain circumstances, this alarm is also output if a braking resistor has not been connected and power is fed
back into the Braking Module.
See also: r3689 (Digital Braking Module Uce fault)
Remedy: - connect a braking resistor.
- check the braking resistor connection.
- check the braking resistor.
- carry out a POWER ON (switch-off/switch-on).
- replace the unit.
A06921 (N) Braking resistor phase unsymmetry
Message value: -
Message class: Braking Module faulted (14)
Drive object: VECTOR_G
Component: Motor Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: - the three resistors of the braking chopper are not symmetrical.
- DC link voltage oscillations caused by fluctuating loads of the connected drives.
Remedy: - check the feeder cables to the braking resistors.
- if required, increase the value for detecting asymmetry (p1364).
See also: p1360 (Braking chopper braking resistor cold), p1362 (Braking chopper activation threshold), r1363
(Braking chopper output voltage), p1364 (Braking chopper resistor asymmetry)
Reaction upon N: NONE
Acknowl. upon N: NONE
F06922 Braking resistor phase failure
Message value: %1
Message class: Braking Module faulted (14)
Drive object: VECTOR_G
Component: Motor Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: A phase failure for the brake resistor was detected.
Fault value (r0949, interpret decimal):
11: Phase U
12: Phase V
13: Phase W
See also: p3235 (Phase failure signal motor monitoring time)
Remedy: Check the feeder cables to the braking resistors.
See also: p1360 (Braking chopper braking resistor cold), p1362 (Braking chopper activation threshold), r1363
(Braking chopper output voltage), p1364 (Braking chopper resistor asymmetry)