Remedy: For fault value = 10, 11, 13, 14, 15, 16, 18, 19, 27:
- check whether there are faults in the safety function alignment between the two monitoring channels (F01655,
F30655) and if required, carry out diagnostics for the faults involved.
- use a Motor Module that supports the required function.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
For fault value = 28:
- use the power unit with the feature "STO via terminals at the Power Module".
For fault value = 29:
- use a Motor Module that supports the required function.
- upgrade the Motor Module software.
- upgrade the Control Unit software.
- If required, parameterize the stop response for PROFIsafe failure to STOP A (p9612 = p9812 = 0).
Note:
CU: Control Unit
ESR: Extended Stop and Retract
MM: Motor Module
SBC: Safe Brake Control
SI: Safety Integrated
SS1: Safe Stop 1 (corresponds to Stop Category 1 acc. to EN60204)
STO: Safe Torque Off / SH: Safe standstill
F30664 Error while booting
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, ENC, HUB, TB30, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component: None Propagation: GLOBAL
Reaction: OFF2
Acknowledge: POWER ON
Cause: An error has occurred during booting.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.
- contact Technical Support.
F30665 SI P2: System is defective
Message value: %1
Message class: Hardware/software error (1)
Drive object: VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: A system defect was detected before the last boot or in the actual one. The system might have been rebooted
(reset).
Fault value (r0949, interpret hexadecimal):
2 hex:
- parameters p9500 and p9300 are not the same (if Safety message C30711 is displayed at the same time).
200000 hex, 400000 hex:
- fault in the actual booting/operation.
Additional values:
- defect before the last time that the system booted.
Remedy: - carry out a POWER ON (switch-off/switch-on).
- upgrade firmware to later version.