4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1834 List Manual (LH2), 07/2016, A5E03263479A
A33470 (F, N) Encoder 3: Soiling detected
Message value: -
Message class: Actual position/speed value incorrect or not available (11)
Drive object: VECTOR_G
Component: Encoder 3 Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: In the case of the alternative encoder system interface on the Sensor Module Cabinet 30 (SMC30), a dirty encoder is
signaled via a 0 signal at terminal X521.7.
Remedy: - check the plug connections.
- replace the encoder or encoder cable.
Reaction upon F: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Acknowl. upon F: IMMEDIATELY
Reaction upon N: NONE
Acknowl. upon N: NONE
F33500 (N, A) Encoder 3: Position tracking traversing range exceeded
Message value: -
Message class: Actual position/speed value incorrect or not available (11)
Drive object: VECTOR_G
Component: None Propagation: GLOBAL
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: For a configured linear axis without modulo correction, the drive/encoder has exceeded the maximum possible
traversing range. The value should be read in p0412 and interpreted as the number of motor revolutions.
For p0411.0 = 1, the maximum traversing range for the configured linear axis is defined to be 64x (+/- 32x) of p0421.
For p0411.3 = 1, the maximum traversing range for the configured linear axis is preset (default value) to the highest
possible value and is +/-p0412/2 (rounded off to complete revolutions). The highest possible value depends on the
pulse number (p0408) and the fine resolution (p0419).
Remedy: The fault should be resolved as follows:
- select encoder commissioning (p0010 = 4).
- reset the position tracking as follows (p0411.2 = 1).
- deselect encoder commissioning (p0010 = 0).
The fault should then be acknowledged and the absolute encoder adjusted.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F33501 (N, A) Encoder 3: Position tracking encoder position outside tolerance window
Message value: %1
Message class: Actual position/speed value incorrect or not available (11)
Drive object: VECTOR_G
Component: None Propagation: GLOBAL
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: When switched off, the drive/encoder was moved through a distance greater than was parameterized in the tolerance
window. It is possible that there is no longer any reference between the mechanical system and encoder.
Fault value (r0949, interpret decimal):
Deviation (difference) to the last encoder position in increments of the absolute value.
The sign designates the traversing direction.
Note:
The deviation (difference) found is also displayed in r0477.
See also: p0413 (Measuring gear position tracking tolerance window), r0477 (Measuring gear position difference)