4 Faults and alarms
4.2 List of faults and alarms
F34801 (N, A) VSM DRIVE-CLiQ: Sign-of-life missing
Message value: Component number: %1, fault cause: %2
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: B_INF
Component: Control Unit (CU) Propagation: LOCAL
Reaction: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY
Cause: A DRIVE-CLiQ communications error has occurred from the Control Unit to the Voltage Sensing Module (VSM).
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the DRIVE-CLiQ connection.
- replace the Voltage Sensing Module (VSM).
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F34802 (N, A) VSM: Time slice overflow
Message value: -
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: Voltage Sensing Module (VSM) Propagation: LOCAL
Reaction: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY
Cause: A time slice overflow has occurred on the Voltage Sensing Module.
Remedy: Replace the Voltage Sensing Module.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F34803 VSM: Memory test
Message value: -
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: Voltage Sensing Module (VSM) Propagation: LOCAL
Reaction: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY
Cause: An error has occurred during the memory test on the Voltage Sensing Module.
Remedy: - check whether the permissible ambient temperature for the Voltage Sensing Module is being maintained.
- replace the Voltage Sensing Module.