EasyManua.ls Logo

Siemens G130 - F35003 TM54 F: Acknowledgment on the Control Unit is required; F35004 TM54 F: communication cycle invalid

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1868 List Manual (LH2), 07/2016, A5E03263479A
F35003 TM54F: Acknowledgment on the Control Unit is required
Message value: -
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component: None Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: A fault on the Terminal Module 54F (TM54) was acknowledged using the safe acknowledgment (p10006).
An additional acknowledgment is also required at the Control Unit.
Remedy: - acknowledge all faults on the Control Unit (BI: p2102).
or
- acknowledge all faults on the drive object TM54F (BI: p2103, p2104 or p2105).
Note:
A fault acknowledgment is triggered with a 0/1 signal.
F35004 TM54F: communication cycle invalid
Message value: Fault cause: %1 bin
Message class: Safety monitoring channel has identified an error (10)
Drive object: B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: - the communication cycle specified in p10000[x] does not correspond with the monitoring cycle of the drive object,
which was specified in p10010[x].
As long as this fault is present, fail safe values are activated in TM54F. All the drives are not enabled.
Fault value (r0949, interpret binary):
If a bit is set in the range bit 0 ... 5, then the following applies:
The communication cycle specified in p10000[x] does not correspond with the monitoring cycle of the drive object
which was specified in p10010[x]. (if only p10000[0] used, then this value must be identical with all monitoring cycles
of the drive objects used in p10010[0..5].)
Bit 0 = 1: p10000[0] does not correspond with the monitoring cycle of p10010[0]
Bit 1 = 1: p10000[1] does not correspond with the monitoring cycle of p10010[1]
..
Bit 5 = 1: p10000[5] does not correspond with the monitoring cycle of p10010[5]
If a bit is set in the range bit 16 ... 21, then the following applies:
Bit 16 = 1: p10000[0] has been selected too low.
Bit 17 = 1: p10000[1] has been selected too low.
..
Bit 21 = 1: p10000[5] has been selected too low.
When using an axis with Basic Safety Functions with TM54F, then the monitoring cycle should be greater than 500us
+ 8 * current controller clock cycles of the drive.
Note:
This error is also signaled if a drive controlled with TM54F is parameterized so that the basic functions are controlled
via TM54F - and simultaneously the extended safety functions or ncSI have been parameterized.
The following applies for fault value = 0:
- since the firmware update of the TM54F it has not been switched off.
- the firmware of the connected TM54F is too old.
See also: p10010 (SI TM54F drive object assignment)