SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1895
4 Faults and alarms
4.2 List of faults and alarms
N35800 (F) TM: Group signal
Message value: -
Message class: General drive fault (19)
Drive object: B_INF, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component: None Propagation: BICO
Reaction: Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge: NONE
Cause: The Terminal Module has detected at least one fault.
Remedy: Evaluates other actual messages.
Reaction upon F: Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowl. upon F: IMMEDIATELY
F35801 (N, A) TM DRIVE-CLiQ: Sign-of-life missing
Message value: Component number: %1, fault cause: %2
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: B_INF, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component: Control Unit (CU) Propagation: BICO
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: A DRIVE-CLiQ communication error has occurred between the Control Unit and the Terminal Module involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy: - check the DRIVE-CLiQ connection.
- replace the component involved.
See also: p9916 (DRIVE-CLiQ data transfer error shutdown threshold slave)
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
A35802 (F, N) TM: Time slice overflow
Message value: -
Message class: Hardware/software error (1)
Drive object: B_INF, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: NONE
Acknowledge: NONE
Cause: A time slice overflow has occurred on the Terminal Module.
Remedy: Replace the Terminal Module.
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE

Table of Contents