SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1937
4 Faults and alarms
4.2 List of faults and alarms
Remedy: In the case of CBE20 SINAMICS Link:
Correct the parameter assignment.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50005 (F) COMM BOARD: Alarm 5
Message value: %1
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 SINAMICS Link:
Sender not found on SINAMICS Link.
Alarm value (r2124, interpret decimal):
0: synchronization to the bus clock cycle unsuccessful.
1 ... 64: address of the sender that was not found.
See also: p8872 (SINAMICS Link PZD receive address)
Remedy: CBE20 SINAMICS Link:
Check the connection to the sender.
Set parameters p8811, p8812[1] to identical values for all participants/nodes.
See also: p8811 (SINAMICS Link project selection), p8812 (SINAMICS Link clock cycle settings)
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50006 (F) COMM BOARD: Alarm 6
Message value: Info. 1: %1, info. 2: %2
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 SINAMICS Link:
The parameter assignment indicates that the sender and the receiver are one and the same. This is not permitted.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = Drive object number from p8872
Info. 2 (decimal) = Index from p8872
See also: p8836 (SINAMICS link node address), p8872 (SINAMICS Link PZD receive address)
Remedy: In the case of CBE20 SINAMICS Link:
Correct the parameter assignment. All p8872[index] must be set to a value not equal to p8836.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY