2 Parameters
2.2 List of parameters
SINAMICS G130/G150
238 List Manual (LH2), 07/2016, A5E03263479A
For bit 12 (only effective if a temperature sensor has not been parameterized):
This bit is used to set the ambient temperature for the motor temperature model 1 (I2t).
The following applies for firmware version < 4.7 SP6 (only bit 0):
- this bit has no function. Temperature model 1 operates with an ambient temperature of 20 °C.
The following applies from firmware version 4.7 SP6 (bits 0 and 12):
- the ambient temperature can be adapted to the conditions using p0613.
Description: Sets the ambient temperature for motor temperature model 1 or 3.
- temperature model 1 (I2t, p0612.0 = 1):
For firmware version < 4.7 SP6 or p0612.12 = 0, the following applies:
The parameter is not relevant.
From firmware version 4.7 SP6 and p0612.12 = 1, the following applies:
The parameter defines the current ambient temperature.
- temperature model 3 (p0612.2 = 1):
The parameter defines the current ambient temperature.
Dependency: Refer to: p0612
Refer to: F07011, A07012
Description: Sets the reduction factor for the overtemperature of the thermal adaptation of the stator/rotor resistance.
The value is a starting value when switching on. Internally, after switch-on, the reduction factor has no effect
corresponding to the thermal time constant.
Dependency: Refer to: p0610
Note: The reduction factor is only effective for p0610 = 12, and refers to the overtemperature.
Description: Sets the fault threshold for monitoring the motor temperature for motor temperature model 1 (I2t).
The following applies for firmware version < 4.7 SP6:
- fault F07011 is output after the fault threshold is exceeded.
- fault threshold for r0034 = 100 % * (p0615 - 40) / (p0605 - 40).
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
- the fault threshold in p0615 is preset when commissioning.
- when a catalog motor with motor temperature model 1 (I2t) is being commissioned for the first time, the threshold
value is copied from p0615 to p5391.
- p5391 is of significance for evaluating the fault threshold.
p0613[0...n] Mot_temp_mod 1/3 ambient temperature / Mod 1/3 amb_temp
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Unit group: 21_1 Unit selection: p0505
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
-40 [°C] 100 [°C] 20 [°C]
p0614[0...n] Thermal resistance adaptation reduction factor / Therm R_adapt red
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [%] 100 [%] 30 [%]
p0615[0...n] Mot_temp_mod 1 (I2t) fault threshold / I2t F thresh
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Unit group: 21_1 Unit selection: p0505
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 220.0 [°C] 180.0 [°C]