SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
265
2 Parameters
2.2 List of parameters
Description: Sets the setpoint for the input signals in the digital input simulation mode.
Dependency: The simulation of a digital input is selected using p0795.
Refer to: p0795
Notice: Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Sets the sampling time for the inputs and outputs of the Control Unit.
Index: [0] = Digital inputs/outputs (DI/DO)
[1] = Not available - analog inputs (AI)
[2] = Not available - analog outputs (AO)
Dependency: The parameter can only be modified for p0009 = 3, 29.
Refer to: p0009
Note: The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
p0796 CU digital inputs simulation mode setpoint / CU DI simul setp
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 2020, 2030,
2031, 2100, 2119, 2120, 2130,
2131, 2132, 2133
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X122.1/X121.1) High Low -
01 DI 1 (X122.2/X121.2) High Low -
02 DI 2 (X122.3/X121.3) High Low -
03 DI 3 (X122.4/X121.4) High Low -
04 DI 4 (X132.1 / -) High Low -
05 DI 5 (X132.2 / -) High Low -
06 DI 6 (X132.3 / -) High Low -
07 DI 7 (X132.4 / -) High Low -
08 DI/DO 8 (X122.9/X121.7) High Low -
09 DI/DO 9 (X122.10/X121.8) High Low -
10 DI/DO 10 (X122.12/X121.10) High Low -
11 DI/DO 11 (X122.13/X121.11) High Low -
12 DI/DO 12 (X132.9/X131.1) High Low -
13 DI/DO 13 (X132.10/X131.2) High Low -
14 DI/DO 14 (X132.12/X131.4) High Low -
15 DI/DO 15 (X132.13/X131.5) High Low -
16 DI 16 (X122.5/X120.3) High Low -
17 DI 17 (X122.6/X120.4) High Low -
20 DI 20 (X132.5/X120.9) High Low -
21 DI 21 (X132.6/X120.10) High Low -
p0799[0...2] CU inputs/outputs sampling time / CU I/O t_sampl
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: C1(3) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2020, 2030,
2031
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 5000.00 [µs] 4000.00 [µs]