2 Parameters
2.2 List of parameters
SINAMICS G130/G150
272 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the configuration for the motor and encoder changeover.
Note: For bit 00:
When the bit is set and the motor has to be changed over, then p0827 must be set differently in the appropriate motor
data sets.
For bit 02:
The bit defines whether, for an EDS changeover, the status signal Gn_ZSW.14 is suppressed (parking encoder
active).
For motor changeover to running motor:
The "flying restart" function should also be activated (p1200) when changing over to a motor that is already running.
Description: Display and BICO output for the status word of the data set switchover.
Note: This parameter is only supplied with up-to-date values if data set changeover has been selected or is running.
For bit 00:
The signal is only influenced when a motor changeover is set via p0827 (unequal bit numbers).
For bit 01:
The signal is only influenced when an encoder changeover is set via p0187, p0188, or p0189.
For bit 02:
A data set changeover is delayed by the time required for the internal parameter calculation.
For bit 04:
A data set changeover is only carried out when the armature short circuit is not activated.
p0833 Data set changeover configuration / DS_chng config
VECTOR_G Can be changed: C2(15) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Data sets Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Contactor changeover from the
application/drive
Application Drive -
01 Pulse suppression by application/drive Application Drive -
02 Suppress drive parking for EDS changeover Yes No -
r0835.0...11 CO/BO: Data set changeover status word / Data set sw ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor changeover active Yes No 8575
01 Encoder changeover active Yes No -
02 Internal parameter calculation active Yes No -
04 Armature short circuit active Yes No -
05 Identification running Yes No -
06 Friction characteristic plot running Yes No -
07 Rotating measurement running Yes No -
08 Motor data identification running Yes No -
10 Wait for pulse suppression Yes No -
11 Wait for motor changeover feedback signal Yes No -