EasyManua.ls Logo

Siemens G130 - r0898.0...14 CO;BO: Control word sequence control; STW seq_ctrl; r0898.0...10 CO;BO: Control word sequence control infeed; STW seq_ctrl INF; r0898.10 CO;BO: Control word sequence control encoder DO; STW seq_ctrl encDO

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
287
2 Parameters
2.2 List of parameters
Description: Display and connector output for the control word of the sequence control.
Note: OC: Operating condition
Description: Display and connector output for the control word of the sequence control for the infeed.
Note: OC: Operating condition
Description: Display and connector output for the control word of the sequence control for encoder drive object.
r0898.0...14 CO/BO: Control word sequence control / STW seq_ctrl
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2501
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enable ramp-function generator Yes No -
05 Continue ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
07 Command open brake Yes No -
08 Jog 1 Yes No 3001
09 Jog 2 Yes No 3001
10 Master control by PLC Yes No -
12 Speed controller enable Yes No -
14 Command close brake Yes No -
r0898.0...10 CO/BO: Control word sequence control infeed / STW seq_ctrl INF
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8720
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
10 Master control by PLC Yes No -
r0898.10 CO/BO: Control word sequence control encoder DO / STW seq_ctrl encDO
ENC Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
10 Master control by PLC Yes No -

Table of Contents