2 Parameters
2.2 List of parameters
Description: Display and connector output for the control word of the sequence control.
Note: OC: Operating condition
Description: Display and connector output for the control word of the sequence control for the infeed.
Note: OC: Operating condition
Description: Display and connector output for the control word of the sequence control for encoder drive object.
r0898.0...14 CO/BO: Control word sequence control / STW seq_ctrl
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2501
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enable ramp-function generator Yes No -
05 Continue ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
07 Command open brake Yes No -
08 Jog 1 Yes No 3001
09 Jog 2 Yes No 3001
10 Master control by PLC Yes No -
12 Speed controller enable Yes No -
14 Command close brake Yes No -
r0898.0...10 CO/BO: Control word sequence control infeed / STW seq_ctrl INF
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8720
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
10 Master control by PLC Yes No -
r0898.10 CO/BO: Control word sequence control encoder DO / STW seq_ctrl encDO
ENC Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
10 Master control by PLC Yes No -