2 Parameters
2.2 List of parameters
SINAMICS G130/G150
298 List Manual (LH2), 07/2016, A5E03263479A
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description: The parameter is used to initiate a reset of the parameters on Terminal Board 30 (TB30).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0161 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value: 0: Inactive
1: Start a parameter reset
100: Start a BICO interconnection reset
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
Description: The parameter is used to initiate a reset of the parameters on Terminal Module 54F (TM54F).
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value: 0: Inactive
1: Start a parameter reset
5: Starts a safety parameter reset
6: Start reset non-safety/safety parameters
100: Start a BICO interconnection reset
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
For p0970 = 5 the following applies:
The password for Safety Integrated must be set.
When Safety Integrated is enabled, this can result in error messages, which then require an acceptance test to be
performed.
Then save the parameters and carry out a POWER ON.
p0970 TB30 reset parameters / TB30 par reset
TB30 Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Factory settings Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 100 0
p0970 TM54F reset parameters / TM54F par reset
TM54F_MA Can be changed: C2(30) Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Factory settings Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 100 0