SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
313
2 Parameters
2.2 List of parameters
Description: Sets the maximum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description: Sets the minimum speed/velocity for the motorized potentiometer.
Note: This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value.
Description: Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency: Refer to: p1037, p1038
Note: The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
Description: Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has been
switched off.
Dependency: Only effective if p1030.0 = 0.
Refer to: p1030
p1037[0...n] Motorized potentiometer maximum speed / MotP n_max
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3020
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1038[0...n] Motorized potentiometer minimum speed / MotP n_min
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3020
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1039[0...n] BI: Motorized potentiometer inversion / MotP inv
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 3020
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1040[0...n] Motorized potentiometer starting value / Mop start value
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3020
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]