SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
317
2 Parameters
2.2 List of parameters
Description: Sets the speed for jog 1.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the speed for jog 2.
Jogging (JOG) is level-triggered, and allows the motor to be incrementally traversed.
Dependency: Refer to: p1055, p1056
Description: Sets the speed limit effective in the setpoint channel.
Dependency: Refer to: p1082, p1083, p1085, p1086, p1088
Description: Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency: Refer to: p1071, r1073, r1078
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1058[0...n] Jog 1 speed setpoint / Jog 1 n_set
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3001, 3030
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1059[0...n] Jog 2 speed setpoint / Jog 2 n_set
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3001, 3030
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1063[0...n] Setpoint channel speed limit / Setp_chan n_lim
VECTOR_G Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3040
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 40000.000 [rpm]
p1070[0...n] CI: Main setpoint / Main setpoint
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3030
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 1024[0]