SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
319
2 Parameters
2.2 List of parameters
Description: Displays the total effective setpoint.
The value indicates the sum of the effective main setpoint and supplementary setpoint.
Description: Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency: Refer to: p1106
Notice: The effective minimum speed is formed from p1080 and p1106.
Note: The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
In order that a stationary motor – after all of the enable signals have been switched on, can operate at the minimum
speed/minimum velocity once all of the enable signals are available, the direction must be entered using one of the
following options:
- direction input via small setpoint.
- direction input by inhibiting the negative or positive direction (p1110, p1111).
Description: Sets the scaling for the maximum speed (p1082).
For a higher-level speed control, this scaling allows the maximum speed to be briefly exceeded.
Dependency: Refer to: p1082
Notice: Continuous operation above a scaling of 100 % is not permitted.
Description: Sets the highest possible speed.
Dependency: For vector control (p1300 = 20 ... 23) the maximum speed is limited to 60.0 / (8.333 x p0115[0] x r0313). This can be
identified by a reduction in r1084. p1082 is not changed in this process due to the fact that the operating mode p1300
can be changed over.
r1078 CO: Total setpoint effective / Total setpoint eff
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3030
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1080[0...n] Minimum speed / n_min
VECTOR_G Can be changed: C2(1), T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [rpm] 19500.000 [rpm] 0.000 [rpm]
p1081 Maximum speed scaling / n_max scal
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3050, 3095
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
100.00 [%] 105.00 [%] 100.00 [%]
p1082[0...n] Maximum speed / n_max
VECTOR_G Can be changed: C2(1), T Calculated: CALC_MOD_ALL Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 2820, 3020,
3050, 3060, 3070, 3095
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 1500.000 [rpm]