SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
325
2 Parameters
2.2 List of parameters
Description: Sets the ramp-function generator type.
Value: 0: Basic ramp-function generator
1: Extended ramp-function generator
Note: Another ramp-function generator type can only be selected when the motor is at a standstill.
Description: Displays the setpoint at the input of the ramp-function generator.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
Description: The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed
(p1082) in this time.
Dependency: Refer to: p1082, p1138
Note: The ramp-up time can be scaled via connector input p1138.
The parameter is adapted during the rotating measurement (p1960 > 0). This is the reason that during the rotating
measurement, the motor can accelerate faster than was originally parameterized.
For U/f control and sensorless vector control (see p1300), a ramp-up time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
Description: Sets the ramp-down time for the ramp-function generator.
The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill
(setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: Refer to: p1082, p1139
p1115 Ramp-function generator selection / RFG selection
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 3001, 3080
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r1119 CO: Ramp-function generator setpoint at the input / RFG setp at inp
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3001, 3050,
3060, 3070, 6300
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1120[0...n] Ramp-function generator ramp-up time / RFG ramp-up time
VECTOR_G Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]
p1121[0...n] Ramp-function generator ramp-down time / RFG ramp-down time
VECTOR_G Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]