2 Parameters
2.2 List of parameters
SINAMICS G130/G150
432 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the magnetizing current of the current model in the q-axis.
Description: Displays the stator current in the q axis after the current actual value tracking.
Description: Sets the signal source for the excitation current actual value
Description: Displays the excitation current actual value that is read in.
Index: [0] = Excitation current of the excitation equipment
[1] = Excitation current for direct excitation
Dependency: Refer to: p0390
Note: The following applies for index 0:
For direct excitation, the value is referred to p0390. For brushless excitation, the value is referred to p0690.
The following applies for index 1:
The value is referred to p0390.
Description: Sets the minimum excitation current.
This means that negative excitation currents can be avoided.
r1638 Current model magnetizing current q axis / I_mod I_mag q-ax
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Unit group: 6_2 Unit selection: p0505
Not for motor type: ASM, PMSM, REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r1639 CO: Current model Isq after actual value tracking / I_mod Isq track
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Unit group: 6_2 Unit selection: p0505
Not for motor type: ASM, PMSM, REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1640[0...n] CI: Excitation current actual value signal source / I_exc_ActVal S_src
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
r1641[0...1] Excitation current actual value / I_exc_act val
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727, 8020
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1642[0...n] Minimum excitation current / Min I_exc
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 50.0 [%] 5.0 [%]