Siemens G130 - p1744[0...n] Motor model speed threshold stall detection; MotMod n_thr stall; p1745[0...n] Motor model error threshold stall detection; MotMod ThreshStall; r1746 Motor model error signal stall detection; MotMod sig stall; p1748[0...n] Motor model lower changeover speed n_set -> n_act; MotMod low n_chng

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
446 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the speed threshold value to detect a stalled motor.
If the adaptation controller output exceeds the parameterized speed difference, then in status word r1408.11 is set =
1.
Dependency: If a stalled drive is detected (r1408.11 = 1), fault F07902 is output after the delay time set in p2178.
Refer to: p2178
Note: Speed monitoring is only effective in operation with a speed encoder (refer to p1300).
Stalling is also identified if steps/jumps occur in the speed signal, which exceed the value in p0492.
Description: Sets the fault threshold in order to detect a motor that has stalled.
If the error signal (r1746) exceeds the parameterized error threshold, then status signal r1408.12 is set to 1.
Dependency: If a stalled drive is detected (r1408.12 = 1), fault F07902 is output after the delay time set in p2178.
Refer to: p2178
Note: Monitoring is only effective in the low-speed range (below p1755 * (100% - p1756)).
Description: Signal to initiate stall detection
Note: The signal is not calculated while magnetizing and only in the low speed range (below p1755 * (100 % - p1756)).
Description: Sets the lower speed for the transition "n_set -> n_act" in encoderless operation.
This value is entered as a percentage referred to p1749.
Dependency: Refer to: p1749, p1752
p1744[0...n] Motor model speed threshold stall detection / MotMod n_thr stall
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: 3_1 Unit selection: p0505
Not for motor type: SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 100.00 [rpm]
p1745[0...n] Motor model error threshold stall detection / MotMod ThreshStall
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 1000.0 [%] 5.0 [%]
r1746 Motor model error signal stall detection / MotMod sig stall
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1748[0...n] Motor model lower changeover speed n_set -> n_act / MotMod low n_chng
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 90.0 [%] 50.0 [%]