Siemens G130 - p1845[0...n] Actual value correction evaluation factor Lsig; ActVal_cor ev Lsig; p1846[0...n] Actual value correction damping factor; ActV_corr D_factor; r1848[0...5] Actual value correction phase currents; ActVal_corr I_ph; r1849[0...5] Actual value correction phase voltages; ActVal_corr U_ph

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
471
2 Parameters
2.2 List of parameters
Description: Sets the weighting factor for the leakage inductance of the L-R element of the actual value correction.
Dependency: Refer to: p0391, p0392, p0393
Note: The load-dependent adaptation of the leakage inductance of the current actual value correction is defined using
p0391 ... p0393.
Description: Sets the damping factor for the actual value correction.
The factor multiplies the T0/Tsig ratio in the feedback branch of the LR element.
Description: Displays phase correction currents as well as the drive converter phase currents
Index: [0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
Description: Displays the phase correction voltages and and the drive converter phase voltages
Index: [0] = Harmonics phase U
[1] = Harmonics phase V
[2] = Harmonics phase W
[3] = Measured value phase U
[4] = Measured value phase V
[5] = Measured value phase W
p1845[0...n] Actual value correction evaluation factor Lsig / ActVal_cor ev Lsig
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 10.00 1.00
p1846[0...n] Actual value correction damping factor / ActV_corr D_factor
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 10.00 1.00
r1848[0...5] Actual value correction phase currents / ActVal_corr I_ph
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r1849[0...5] Actual value correction phase voltages / ActVal_corr U_ph
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -