2 Parameters
2.2 List of parameters
SINAMICS G130/G150
484 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the speed to determine the saturation characteristic and the encoder test.
The percentage value is referred to p0310 (rated motor frequency).
Dependency: Refer to: p0310, p1959
Refer to: F07983
Note: The saturation characteristics should be determined at an operating point with the lowest possible load.
Description: Displays the magnetizing currents of the identified saturation characteristic.
The values are referred to r0331.
After they have been determined, the values are transferred to p0366 ... p0369.
Index: [0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Dependency: Refer to: r0331
Description: Displays the magnetizing inductances of the identified saturation characteristic.
The values are referred to r0382.
Index: [0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Dependency: Refer to: r0382
p1961 Saturation characteristic speed to determine / Sat_char n determ
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Motor identification Unit group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
26 [%] 75 [%] 40 [%]
r1962[0...4] Saturation characteristic magnetizing current / Sat_char I_mag
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Motor identification Unit group: - Unit selection: -
Not for motor type: PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1963[0...4] Saturation characteristic magnetizing inductance / Sat_char L_main
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Motor identification Unit group: - Unit selection: -
Not for motor type: PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]