SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
535
2 Parameters
2.2 List of parameters
Description: Selects the faults for which the fault response should be changed
Dependency: The fault is selected and the required response is set under the same index.
Refer to: p2101
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description: Sets the fault response for the selected fault.
Value: 0: NONE
Dependency: The fault is selected and the required response is set under the same index.
Notice: For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
Note: Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description: Sets the fault response for the selected fault.
Value: 0: NONE
1: OFF1
2: OFF2
3: OFF3
5: STOP2
6: Internal armature short-circuit / DC braking
7: ENCODER (p0491)
Dependency: The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice: For the following cases, it is not possible to re-parameterize the fault response to a fault:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- fault response is not permissible for the set fault number.
p2100[0...19] Change fault response fault number / Chng resp F_no
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 8050, 8075
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p2101[0...19] Change fault response response / Chng resp resp
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP, TM31,
TM120, TM150, TB30,
TM54F_MA,
TM54F_SL, ENC, HUB
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 8050, 8075
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 0 0
p2101[0...19] Change fault response response / Chng resp resp
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 8050, 8075
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 7 0