2 Parameters
2.2 List of parameters
Description: Display and connector output of the smoothed speed actual value for messages.
Dependency: Refer to: p2153
Description: Sets the torque threshold value for the messages:
"Torque setpoint < torque threshold value 1 and n_set reached" (BO: r2198.9)
"Torque setpoint < torque threshold value 1" (BO: r2198.10)
"Torque setpoint > torque threshold value 1" (BO: r2198.13)
Dependency: Refer to: p2195, r2198
Description: Sets the speed threshold for the message "Motor blocked" (BO: r2198.6).
Dependency: Refer to: p0500, p2177, r2198
Refer to: F07900
Note: The following applies for encoderless vector control for induction motors:
At low speeds in open-loop speed controlled operation (see p1755, p1756), a blocked motor cannot be detected.
The following applies for encoderless vector control for permanent magnet synchronous motors:
At low speeds in open-loop speed controlled operation (see p1755, p1756), a blocked motor can only be detected if
p2175 = p1755, and p1750.6 is set to 1.
Description: Sets the delay time for the message "Motor blocked" (BO: r2198.6).
Dependency: Refer to: p0500, p2175, r2198
Refer to: F07900
r2169 CO: Actual speed smoothed signals / n_act smth message
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8010
P-Group: Messages Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p2174[0...n] Torque threshold value 1 / M_thresh val 1
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 5.13 [Nm]
p2175[0...n] Motor blocked speed threshold / Mot lock n_thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 120.00 [rpm]
p2177[0...n] Motor blocked delay time / Mot lock t_del
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 65.000 [s] 1.000 [s]