Siemens G130 - p2186[0...n] Load monitoring torque threshold 1 lower; M_thresh 1 lower; p2187[0...n] Load monitoring torque threshold 2 upper; M_thresh 2 upper; p2188[0...n] Load monitoring torque threshold 2 lower; M_thresh 2 lower; p2189[0...n] Load monitoring torque threshold 3 upper; M_thresh 3 upper

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
558 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2186 < p2185
Refer to: p2182, p2185
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2187 > p2188
Refer to: p2183, p2188
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note: The lower envelope curve is defined by p2186, p2188 and p2190.
Description: Sets the speed/torque / velocity/force envelope curve for the load monitoring.
Dependency: The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
Note: The upper envelope curve is defined by p2185, p2187 and p2189.
p2186[0...n] Load monitoring torque threshold 1 lower / M_thresh 1 lower
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2187[0...n] Load monitoring torque threshold 2 upper / M_thresh 2 upper
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]
p2188[0...n] Load monitoring torque threshold 2 lower / M_thresh 2 lower
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 0.00 [Nm]
p2189[0...n] Load monitoring torque threshold 3 upper / M_thresh 3 upper
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Nm] 20000000.00 [Nm] 10000000.00 [Nm]