SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
567
2 Parameters
2.2 List of parameters
Description: Display and BICO output for the status word of the fixed value selection of the technology controller.
Description: Displays the number of the selected fixed setpoint of the technology controller.
Dependency: Refer to: r2224
Description: Sets the configuration for the motorized potentiometer of the technology controller.
Dependency: Refer to: r2231, p2240
Notice: The following prerequisites must be fulfilled in order to be able to save the setpoint in a non-volatile fashion:
- Firmware with V2.3 or higher.
- Control Unit 320 (CU320) with hardware version C or higher (module with NVRAM).
Note: For bit 00:
0: The setpoint for the motorized potentiometer is not saved and after ON is entered using p2240.
1: The setpoint for the motorized potentiometer is saved and after ON is entered using r2231. In order to save in a
non-volatile fashion, bit 03 should be set to 1.
For bit 02:
0: Without initial rounding-off
1: With initial rounding-off.
The selected ramp-up/down time is correspondingly exceeded. The initial rounding-off is a sensitive way of
specifying small changes (progressive reaction when keys are pressed). The jerk for initial rounding is independent
of the ramp-up time and only depends on the selected maximum value (p2237).
r2225.0 CO/BO: Technology controller fixed value selection status word / Tec_ctr FixVal ZSW
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller fixed value selected Yes No 7950,
7951
r2229 Technology controller number actual / Tec_ctrl No. act
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 7950
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p2230[0...n] Technology controller motorized potentiometer configuration / Tec_ctr mop config
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0100 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Data save active Yes No -
02 Initial rounding-off active Yes No -
03 Non-volatile data save active for p2230.0 =
1
Yes No -
04 Ramp-function generator always active Yes No -