Siemens G130 - p2297[0...n] CI: Technology controller maximum limit signal source; Tec_ctrMaxLimS_src; p2298[0...n] CI: Technology controller minimum limit signal source; Tec_ctrl min_l s_s; p2299[0...n] CI: Technology controller limit offset; Tech_ctrl lim offs; p2306 Technology controller system deviation inversion; Tec_ctr SysDev inv

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
578 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the signal source for the maximum limiting of the technology controller.
Dependency: Refer to: p2291
Description: Sets the signal source for the minimum limiting of the technology controller.
Dependency: Refer to: p2292
Description: Sets the signal source for the offset of the output limiting of the technology controller.
Description: Setting to invert the system deviation of the technology controller.
The setting depends on the type of control loop.
Value: 0: No inversion
1: Inversion
Caution: If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note: The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the technology controller).
- if the actual value increases with increasing motor speed, then the inversion should be switched out.
- if the actual value decreases with increasing motor speed, then the inversion should be set.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
p2297[0...n] CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 2291[0]
p2298[0...n] CI: Technology controller minimum limit signal source / Tec_ctrl min_l s_s
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 2292[0]
p2299[0...n] CI: Technology controller limit offset / Tech_ctrl lim offs
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p2306 Technology controller system deviation inversion / Tec_ctr SysDev inv
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0