2 Parameters
2.2 List of parameters
SINAMICS G130/G150
590 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the absolute value of the last synchronization deviation that was determined.
Index: [0] = Milliseconds
[1] = Days
Description: Sets the tolerance for time of day synchronization.
When this tolerance is exceeded, an appropriate alarm is output.
Dependency: Refer to: A01099
Description: Sets the delay time for external fault 3.
Dependency: Refer to: p2108, p3111, p3112
Refer to: F07862
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Refer to: F07862
r3108[0...1] UTC synchronization deviation / UTC sync_dev
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p3109 UTC synchronization tolerance / UTC sync tol
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p3110 External fault 3 switch-on delay / Ext fault 3 t_on
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2546
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p3111 BI: External fault 3 enable / Ext fault 3 enab
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP, TM31,
TM120, TM150, TB30,
TM54F_MA,
TM54F_SL, ENC, HUB
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2546
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1