SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
591
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Refer to: F07862
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
p3111[0...n] BI: External fault 3 enable / Ext fault 3 enab
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: -
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p3112 BI: External fault 3 enable negated / Ext flt 3 enab neg
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP, TM31,
TM120, TM150, TB30,
TM54F_MA,
TM54F_SL, ENC, HUB
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2546
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p3112[0...n] BI: External fault 3 enable negated / Ext flt 3 enab neg
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: -
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0