2 Parameters
2.2 List of parameters
For bit 11:
The infeed is faulted or has failed. Check the infeed and the surroundings (line supply, filter, reactors, fuses, ...).
Check the closed-loop infeed control.
For bit 15:
Group fault. Determine the precise cause of the fault using the commissioning tool.
Description: Displays the global status word for messages.
The appropriate bit is set if at least one message is present at the drive objects.
Note: The status bits are displayed with delay.
Description: Displays the drive object number of the initiating drive object for this fault as integer number.
Value = 63:
The fault was initiated by the drive object itself.
Dependency: Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3120, r3122
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
Description: Sets the signal source for the automatic acknowledgment of Control Unit faults.
BI: p3116 = 0 signal
Acknowledgeable faults are automatically acknowledged on the Control Unit.
Control Unit faults with LOCAL propagation are passed on to the first active drive object.
BI: p3116 = 1 signal
Acknowledgeable faults are not automatically acknowledged on the Control Unit.
Control Unit faults with LOCAL propagation are not passed on.
Dependency: Refer to: p2102, p2103, p2104, p2105, p3981
Note: When selecting a standard telegram, the BICO interconnection for control signal STW1.10 (master control by PLC) is
automatically established.
r3114.9...11 CO/BO: Messages status word global / Msg ZSW global
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
09 Group alarm present Yes No 8065
10 Group fault present Yes No 8060
11 Safety group message present Yes No -
r3115[0...63] Fault drive object initiating / F DO initiating
All objects Can be changed: - Calculated: - Access level: 3
Data type: Integer32 Dyn. index: - Func. diagram: 8050, 8060
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p3116 BI: Suppress automatic acknowledgment / Ackn suppress
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0