Siemens G130 - r3804 CO: Sync-line-drive target frequency; Sync f_target; r3805 CO: Sync-line-drive frequency difference; Sync f_diff; p3806[0...n] Sync-line-drive frequency difference threshold value; Sync f_diff thresh; r3808 CO: Sync-line-drive phase difference; Sync phase diff

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
618 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the target frequency for the line-drive synchronization.
Dependency: Refer to: A07941
Description: Displays the frequency difference between the measured target frequency and output frequency of the gating unit of
the closed-loop control for line-drive synchronization.
Description: Sets the threshold value of the frequency difference to activate the closed-loop phase control for line-drive
synchronization.
The closed-loop phase control is activated (r3819.6 = 1), if the frequency difference is less that the threshold value.
Description: Displays the phase difference between the measured target phase and phase of the gating unit of the closed-loop
control for line-drive synchronization.
Description: Sets the phase setpoint for the line-drive synchronization.
r3804 CO: Sync-line-drive target frequency / Sync f_target
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3030, 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
r3805 CO: Sync-line-drive frequency difference / Sync f_diff
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
p3806[0...n] Sync-line-drive frequency difference threshold value / Sync f_diff thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 1.00 [Hz] 0.10 [Hz]
r3808 CO: Sync-line-drive phase difference / Sync phase diff
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: p2005 Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
p3809[0...n] Sync-line-drive phase setpoint / Sync phase setp
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-180.00 [°] 179.90 [°] 0.00 [°]